Short answer, inverter on battery mode: Sometimes the grid is available but the inverter keeps running from the battery. Hybrid inverter manuals list three main reasons.
1. Input breaker tripped
If the screen shows input voltage as 0 and the green LED flashes, the manuals say the input protector has tripped. Check whether the AC breaker has tripped and whether the AC wiring is connected well.
2. Poor AC power quality
With a green LED flashing, the manuals mention insufficient quality of AC power, for example from a generator. Check whether AC wires are too thin or too long, whether the generator is working well, and whether the input voltage range setting (UPS or Appliance) is correct.
3. Output source priority setting
If the output priority is set to “Solar First” (or “Battery First” on the Growatt SPF ES), the inverter will use solar/battery even when mains is present. The manuals’ fix is to change the output source priority to “Utility first” if you want the grid to supply the load.
Many people choose Solar First on purpose to save electricity. Change it only if you want grid power to take priority.
Quick checklist
- Is the AC input breaker on?
- Are input wires firm, not too thin or too long?
- On a generator, is it running steadily?
- Is the input range (UPS/Appliance) set correctly?
- What is the output priority setting?
Safety: Inverters, batteries and solar panels carry dangerous voltages. Only do checks from outside the unit. For anything inside, contact an authorised service centre.
Related: free solar tools and the Error Code Finder.
Roman Urdu mein: Bijli ho aur inverter phir bhi battery par chale to: input breaker trip to nahi, taarein patli ya lambi to nahi, generator theek chal raha hai, UPS/Appliance range sahi hai, aur setting "Solar First" to nahi. Grid se chalana ho to "Utility First" karein.
Frequently asked questions
Is Solar First a fault?
No, it is a setting. With Solar First the inverter prefers solar even when mains is present.
Why does a generator cause this?
The manuals mention insufficient AC power quality from shore or generator supply.
Sources: troubleshooting and warning tables in the Growatt SPF 3500/5000 ES, Fronus Infineon 3.5/5.5KVA and Inverex Aerox 1.2 to 3.2KW user manuals. Copies: Growatt SPF ES manual Fronus Infineon manual Inverex Aerox manual (hosted by third parties, not by the brands).